Get the kit for your summer jobs sorted now: ask us for a price and reserve the units.

Ventilation airflow calculator

Premises, home or car park: enter the use and the number of people or the floor area and we give you the minimum outdoor airflow in l/s and m³/h, with the sum and the clause of the regulation.

I'd rather you worked it out696 87 57 54

In short

It depends on the use. In premises and buildings, Spain's RITE applies: each use has an indoor air category (IDA) and each category a flow per person; an office, for example, 12.5 l/s per person. In homes, the CTE, section HS 3 applies: a set flow per bedroom, living room and bathroom or kitchen, depending on the number of bedrooms. Car parks, storage rooms and bin stores have their own table in HS 3.

The calculator does the sum with those tables and tells you where each figure comes from. It runs in your browser: nothing is sent until you tap WhatsApp.

Then, the unit

With the airflow you can choose the heat recovery unit or fan. Send us the airflow, the use and where the unit goes and we'll give you a price in writing.

What it doesn't calculate

Only the minimum outdoor airflow. It doesn't size ducts, grilles or pressure drops, and it doesn't replace the design when the job needs one. Where smoking is allowed, the RITE asks for at least double; the calculator doesn't cover that.

Frequently asked questions

What is the IDA category?

The indoor air quality the RITE requires for each building use: IDA 1, the highest (hospitals, clinics, laboratories and nurseries); IDA 2, good (offices, classrooms, residences, museums and swimming pools); IDA 3, medium (shops, hospitality, cinemas, gyms). The higher it is, the more outdoor air per person.

l/s or m³/h?

The regulations give airflow in litres per second (l/s, the same as dm³/s); fan and heat recovery catalogues usually give it in m³/h. 1 l/s is 3.6 m³/h.

When is a heat recovery unit required?

In an air-conditioned building, the RITE requires the energy of the air exhausted by fans to be recovered when it exceeds 0.28 m³/s, about 1,008 m³/h (IT 1.2.4.5.2). The calculator tells you when your airflow goes over that.

Does the calculator replace the design?

No. It's indicative and non-binding: the final airflow is set by the designer or an authorised technician with the building in front of them.

You might also like

Ventilation and heat recovery

Price in writing: ask us

Fresh air without throwing away the cooling or heating you've already paid for.

See the page

Brands and orders

Price in writing: ask us

The brands we supply and how to place an order.

See the page

Tell us what you need and we'll give you a price

Send us part numbers, capacities and quantities, or the design, on WhatsApp. We'll reply with price and availability, in writing.

Message us on WhatsApp 696 87 57 54

Phone · WhatsApp
+34 696 87 57 54
Email
Opening hours
Monday to Friday, 9:00 to 20:00; Saturday, 12:00 to 15:00.
Where we are
Calle Atenas 53, 29006 Málaga

Price in writingIn writing, with availability

Call Ask for a price